Specifications
Ammonia Gas Monitor – Multi Zone
24
Instruction 3015-5113
Typical AGM-MZ Relay 1 and Relay 2 Wiring
Strobe or
Horn
NO
COMMON
NC
L
I
N
E
N
E
U
T
R
A
L
Leak / Spill / Evacuate / Fault
Red* Yellow*
RELAY
Normal configuration:
Strobes are usually connected
to the Leak relay (#1)
Horns are usually connected
to the Spill relay (#2).
External Power:
AC < 250V
DC < 15W
Note: The device does not power
accessories; power must come from
an external source.
LINE POWER
*The colors correspond to
the LEDs on the front of the
case.
Jumper the ‘Neutral’ of the input power connector to the ‘Common’ on the relay block. Connect one end of
strobe or horn to the ‘NO’ of whichever level of alarm is appropriate for application. The other end of strobe or
horn is connected to the ‘Line’ of the input power connector (5 A maximum).