Specifications

Ammonia Gas Monitor – Multi Zone
10
Instruction 3015-5113
Installation Considerations
Warnings & Cautions
WARNING: Explosion hazard! Do not mount the AGM-MZ in an area that may contain
flammable liquids, vapors or aerosols. Operation of any electrical equipment in such an
environment constitutes a safety hazard.
WARNING: Shock hazard! Always disconnect AC power before accessing the interior
of the monitor.
CAUTION: Drilling holes in the AGM-MZ enclosure may damage the unit and will void
the warranty. Please use the knockouts provided for electrical connections.
CAUTION: The AGM-MZ contains sensitive electronic components that can be easily
damaged. Do not touch nor disturb any of these components.
Inspection
The AGM-MZ has been thoroughly inspected and tested prior to shipment from the factory. Nevertheless, it is
recommended that the monitor be re-checked prior to installation. Inspect the outside of the enclosure to
make sure there are no obvious signs of shipping damage. Open the enclosure and inspect the interior of the
monitor for loose components that may have become dislodged during shipment. If damage is discovered,
please contact the nearest Bacharach Service Center for assistance.
Location of the Monitor
The AGM-MZ should be centrally located in the facility and should be easily accessible for visual monitoring
and servicing. Intake sample lines can be up to 500 feet in length, but it is important to remember that
sampling cycle time is proportional to the total number and length of individual sample lines.
Dirt, grease, and oils can adversely affect the operation of the AGM-MZ. The monitor should be installed out
of direct sunlight in a clean, dry area that is not subject to temperature or humidity extremes. Installation of
the monitor in a mechanical room is acceptable provided reasonable environmental conditions exist. If there
is a question, consider installing the unit outside of the mechanical room in a cleaner area of the facility.
The location should allow the monitor to be easily accessible for visual monitoring and servicing.