Jumper the “Live/Positive” line of an external power source (DC devices) or the monitor’s AC input (AC 
devices) to the “Common” terminal on the relay connector.  
Connect the “Live/Positive” end of the strobe or horn to the “NO” terminal of whichever level of alarm is 
appropriate for the application. 
For protection, install an in-line fuse of the appropriate size and design for the external alarm device being 
used. 
The other end of the strobe or horn is connected to the “Neutral/Negative” leg of the external power 
source (DC devices) or monitor’s AC input (AC devices).   
Figure 2-14. Typical AC External Alarm Relay 1 Wiring 
Figure 2-15. Typical DC External Alarm Relay 1 Wiring 