Owner's Manual
Multi-Zone Gas Monitors 
P/N: 3015-5074 Rev 11    23 
Figure 2-12. Optional Dual 4-20 mA DC Output Board and Connector 
2.10. Connecting External Alarms 
2.10.1. Overview 
The MZ monitor includes four SPDT relays whose contacts are rated 2 A at 250 VAC (inductive) and 5 A at 
250 VAC (resistive). These relays are used for the connection of external alarm devices that are activated 
when the relay is energized. The relays are factory assigned to energize under the following conditions: 
  Relay #1  Leak  Alarm Point 100 ppm 
  Relay #2  Spill  Alarm Point 300 ppm 
  Relay #3  Evacuate  Alarm Point 500 ppm 
  Relay #4  Fault  System Fault Event 
2.10.2. Connection 
Use the conduit or any of the remaining service knockouts to gain cable access to the interior of the monitor. 
Locate the relay connector (see Figure 2-3 on page 13) and remove it from the circuit board. Secure the 
leads to the connector orienting them as shown in the diagram below. When you are through securing the 
connections, carefully plug the connector back onto the circuit board. 
Figure 2-13. MZ Monitor Relay Connector 
Each relay may be connected as normally open (NO), or normally closed (NC). The relay contacts are 
rated 2 A at 250 VAC (inductive) and 5 A at 250 VAC (resistive). 
Power for the alarm devices connected to the relay contacts may be supplied by an external 24 VDC 
power source or the monitor’s AC input terminals. In the first wiring diagram, power to this device is being 
tapped off the monitor’s AC input. In the second wiring diagram, power is supplied from an external 
power source. 