Owner's Manual
Multi-Zone Gas Monitors
6 P/N: 3015-5074 Rev 11
NOTE: The pickup points located on the floor in the above illustration are examples for
refrigerants which are heavier than air. Placement of pickup points should be determined
based on characteristics of the gas being monitored and ambient conditions of the sampling
area. (Air=28.9 g/mole, CO
2
=44.0 g/mole, NH
3
=17.0 g/mole, and halogens = 100+ g/mole.)
1.6. Specifications
HGM-MZ Specifications
Product Type
Multiple refrigerant gases
and multiple area monitoring system for low level continuous
monitoring of CFC, HCFC and HFC refrigerant gases used in most commercial
refrigera
tion systems. System design supports compliance to the refrigerant monitoring
requirements of ANSI/BSR ASHRAE 15-2007 and ASHRAE Safety Code 34-2007.
Sensitivity All gases 1 ppm
Measuring Range All gases 0 to 10,000 ppm
Accuracy
1
±1 ppm ±10% of reading from 0-1000 ppm
(R11, R22, and R113 ±10 ppm ±15% of reading 0-1000 ppm)
Gas Library
CFC: HFP, R-11, R-12, R-113, R-114, R-502
HFC: R125, R-134a, R236FA, R245Fa, R32, R-404a (HP62), R-407a, R-407c
(AC9000), R-410a (AZ20), R422a, R422d, R427a, R-507 (AZ50), R-508b
(SUVA95)
HCFC: R-123, R-124, R21, R-22, R227, R-23, R-401a (MP39), R-402a (HP80),
R-402b (HP81), R-408a, R-409a, R-500, R-503
Halon: H1211, H1301, H2402
Other: FA188, FC72, H1234YF, N1230, R424A, R426A, R438A, CUSTOM
AGM-MZ Specifications
Product Type
The AGM-MZ provides multiple area monitoring system for low level continuous
monitoring of Ammonia gases used in m ost comm ercial s ystems .
Sensitivity 20 ppm
Measuring Range 25 to 10,000 ppm
Accuracy
1
±10 ppm ±10% of reading from 0-10,000 ppm
Gas Library Ammonia (NH
3
)/R-717
CO
2
-MZ Specifications
Product Type
The CO
2
-MZ provides multiple area monitoring for low level continuous monitoring of
carbon dioxide gases used in most commercial systems. System design supports
compliance to the gas monitoring requirements of ANS/BSR ASHRE 15-1994.
Sensitivity 10 ppm
Measuring Range 300-8,000 ppm
Accuracy
1
±5 PPM ±5% of reading from 300-1000 ppm, ±10% of reading from 1001-3000 ppm
Gas Library Carbon Dioxide (CO
2
)/R-744
1
At reference environmental conditions (25°C, 45% RH non-condensing, 1 ATM)