Specifications
16 Instruction 3015-4256
The DIAGNOS Function (Page 22).
GAS TYPE – Used to select of any one of the refrigerant gas types listed for
monitoring. (See the gas library in the Specifications section.) Factory default is
R-134a. Use the Keypad to select the desired gas type, and then press
ENTER to save the selection and return to the previous screen.
LEAKLVL – Sets the Leak Alarm level, adjustable from 1 to 300 ppm.
Factory default is 100 ppm. Note that the Leak Alarm level cannot be set
higher than either the Spill or Evacuate Alarm levels. Refer to Appendix for
recommended alarm settings for other gases. Use the Keypad to set the
desired Leak Alarm level, and then press ENTER to save that level and
return to the previous screen.
SPILLLVL – Sets the Spill Alarm level, adjustable from no lower than the
Leak Alarm level to a maximum value of 500 ppm, but not higher than the
Evacuate Alarm level. Factory default is 300 ppm. Refer to Appendix for
recommended alarm settings for other gases. Use the Keypad to set the
desired Spill Alarm level, and then press ENTER to save that level and return
to the previous screen.
EVACLVL – Sets the Evacuate Alarm level, adjustable from no lower than
the Spill Alarm level to 9999 ppm. Factory default is 500 ppm. Refer to
Appendix for recommended alarm settings for other gases. Use the Keypad
to set the desired spill level alarm level, and then press ENTER to save that
level and return to the previous screen.
LOG INT – Sets the interval at which measurements are logged to memory
from 1 to 9999 minutes. Factory default is 10 minutes. Note that the logged
measurements can be viewed using the PPM LOG function. Use the Keypad
to enter the desired value, and then press ENTER to save that value and
return to the previous screen.
LOOP – Adjusts the loop factor of the 4–20 mA current loop. Factory default
is 0.016 mA per ppm, which provides an output range of 0 ppm (4 mA) to
1,000 ppm (20 mA). Use the Keypad to set the desired loop factor, and then
press ENTER to save that value and return to the previous screen.
To facilitate loop zero and span checking, note that when the LOOP function
is selected the loop output is set to 20 mA, and upon exiting this function the
loop output is set to 4 mA.
AUDALRM – Allows the monitor’s internal audible alarm to be associated
with any function of the monitoring system. Factory default is OFF. Use the
Keypad to select the desired audible alarm function, and then press ENTER
to save that value and return to the previous screen.
Audible Alarm Settings: OFF, ANY ALARM, SYSTEM FAULT, LEAK ALARM,
SPILL ALARM, EVAC ALARM, MONITOR STOPPED
NOTE: MONITOR STOPPED indicates there is a critical system fault, and
the monitor is no longer functioning correctly.
CLOCK – Sets the monitor’s date and time. Use the Keypad to enter the
correct date and time, and then press ENTER to save those values and
return to the previous screen. Note that time is displayed in a 24 hour format,
while the date is displayed as mm/dd/yy.
L
OG INTERVAL IS
0010 min
E
DIT LOOP FACTOR
0.016 ma/PPM
A
UDIBLE ALARM IS
OFF
S
ET DATE & TIME
11/10/08 15:30
S
ELECT GAS TYPE
R134A
E
DIT EVAC LEVEL
0500 PPM
E
DIT SPILL LEVEL
0300 PPM
E
DIT LEAK LEVEL
0
100 PPM