Specifications
1.800.736.4666
BACHARACH
48
SPECIFICATIONS
NDIR, Multi-Zone Sample Draw Systems
Refrigerants:
HGM300 Model CFC: R-11, R-12, R-113, R-114, R-502,
HFC: R-404a (HP62), R-407a, R-407c
(AC9000), R-134a, R-410a (AZ20),
R-507 (AZ50), R-508b (SUVA95)
HCFC: R-22, R-123, R-124, R-500, R-503,
R-401a (MP39), R-402a (HP80),
R-40b (HP81), R-408a, R-409a, R-23
HALON:1301
Measuring Range: 0 to 10,000 ppm
AGM300 Model R-700 (Ammonia)
Measuring Range: 25 to 10,000 ppm
Inputs: 4 point standard, expandable to 16 points in
4 point increments
Output Signal: 4-20mA DC (optional)
Detector Type: Non-dispersive infrared
Measuring Range: All gases 0 to 10,000 ppm
Sensitivity: All gases 1 ppm
Accuracy: All gases ±10 ppm from 0 to 100 ppm,
±10% of reading from 100 to 10,000 ppm
Front Panel Display: Green LED indicates when unit is operating
properly
Red LED indicates when any monitored point
is above its alarm setting
Yellow LED indicates a clogged sample line or
other system fault
Response Time: 5 to 120 seconds, depending on tube length
and gas concentration
Max. Monitoring Distance: Up to 500 feet from measuring point to
monitor
Power: 120 / 230VAC, 50 / 60 Hz
Size/Weight: 17" L x 12" W x 5.5" D / 15 lbs
(43.18cm L x 30.48cm W x 13.97cm D / 6.8 Kg)
ORDERING INFORMATION for Monitors
Code A Model Number
HGM300 For use with CFC, HFC, HCFC and Halon Refrigerants
AGM300 For use with Ammonia Refrigerants
Code B Number of zones and connection type
-01 4 Zones with barb fittings (Standard)
-02 8 Zones with barb fittings
-03 12 Zones with barb fittings
-04 16 Zones with barb fittings
-11 4 Zones with metal tube fittings
-12 8 Zones with metal tube fittings
-13 12 Zones with metal tube fittings
-14 16 Zones with metal tube fittings
Code C Input Power Type
-1 120VAC / 60 Hz (Standard)
-2 240VAC / 50 Hz
-3 100VAC / 50 Hz
Code D Analog Output
-0 None (Standard)
-1 Dual Loop 4 to 20 mAdc
Code E Water Trap
-1 Water Trap (Standard)
Code F High Accuracy Calibration
-0 None (Standard)
-1 Consult Factory
OPTIONS / ACCESSORIES
PART NO. DESCRIPTION
3015-4121 120VAC surge protection
3015-4122 230VAC surge protection
3015-4123 4-20 mA dc surge protection (two required)
3015-3069 Visual alarm 120VAC
3015-3070 Audio alarm 120VAC
3015-3076 Audio / Visual alarm 120 VAC
3015-3423 Annual maintenance kit
3015-3235 Air sample tubing (250’per roll)
When ordering this product, you must specify 6 codes: These 6 codes will
build up a part number. Codes must be listed in the following sequence.
Code A- Model Number
Code B- Number of Zones
Code C- Input Power Type
Code D- Analog (Yes / No)
Code E- Water Trap (Always Included)
Code F- High Accuracy Calibration
For example, to order a 4-zone, 120VAC Ammonia Monitor with a standard
analog output and standard calibration, you would order a:
AGM300-01-1-0-1-0
Remote Display Modules, options and accessories must be ordered as
separate line items.
ORDERING INFORMATION for Display Modules
3015-2875 RDM800 120VAC / 60 Hz
3015-2885 RDM800 240VAC / 50 Hz
3015-4195 ADM800 120VAC / 60 Hz
3015-4196 ADM800 240VAC / 50Hz
SPECIFICATIONS REMOTE DISPLAY MODULES
Model RDM800 Model Compatible with HGM300 Model
ADM800 Model Compatible with AGM300 Model
Inputs: Accepts from one to four inputs via RS-485
from up to four HGM300 Refrigerant Monitors
Display: Backlit LCD displays the measured point in
ppm
Trend Mode / Data logging: User may select a graphical display of the
ppm trend for any measured point
(100 data entries per point)
Alarm Indications: Channel display flashes, red light flashes,
alarm signal sent via RS-485
Input Fault Indication: Yellow light flashes and the LCD indicates
location of input fault
Max. Monitoring Distance: Maximum of 4,875 wiring feet from the
furthest HGM300 to the RDM800 Display
Power: 120 / 240VAC, 50 / 60 Hz
Size/Weight: 11" L x 10" W x 3" D / 5 lbs (wall mounted)
System design supports compliance to the refrigerant monitoring requirements of ANSI / BSR ASHRAE 15. Certified in compliance to UL #3101-1, CE
#EN613262, and EN61010-1.