Specifications
1.800.736.4666
BACHARACH
26
The FloRite 500 and 600 are rotating-vane anemometers for air velocity and volume flow rate
measurements. Both instruments have been designed with ease of set up and operation in mind.
The user can choose measurements to be displayed on its LCD in either Metric or Imperial units
by means of a slide switch located inside the battery compartment. Both instruments are designed
for supply and return airflow applications in heating, ventilating and air conditioning
systems making air measurement quick, reliable and accurate.
ORDERING INFORMATION
Florite 500
The FloRite 500 measures air velocity by pressing and
holding down the pushbutton located on the side of the
handle. The average air velocity is automatically calculated
and the digital display updated every 3 seconds over the time
period that the pushbutton is held down.
Features
• Air velocity measurement
• Metric or Imperial display of units
• Simple one button control
• Large clear LCD with fast response
• Self-diagnostic function
Applications
• Residential HVAC commissioning and balancing
• Safety checks for fume and ventilation hoods
• Comfort conditions
• Environmental monitoring
Florite 600
The FloRite 600 measures air velocity or
volume flow rate averaged over a 3
second period by momentarily depressing
the pushbutton located on the side of the
handle. When the pushbutton is pressed
and held down, however, the instrument
automatically calculates and displays the
average air velocity or volume flow rate
over the time period that the pushbutton is
held down for a maximum of 12 minutes.
This allows the user to traverse large grilles
and ducts in one sweep and to have the
average value displayed automatically,
thereby saving on operator time and
inconvenience of manual calculations.
Features
• Air velocity measurement
• Air velocity or air volume flow rate measurement
• Metric or Imperial display of units
• Simple one button control
• Large clear LCD with fast response
• Self-diagnostic function
Applications
• Residential HVAC commissioning and balancing
• Safety checks for fume and ventilation hoods
• Comfort conditions
• Environmental monitoring
* The Airhood Kit is used to convert the FloRite into an air volume flow
meter. This kit includes an 11.2" x 9.2" rectangular hood, 7.0" diameter
circular hood, protective carrying case, calibration curves, and instructions.
Velocity Range 50 to 6000 ft/min (0.25 to 30 m/sec)
Accuracy Better than ±1% of reading, ±1 digit
Dimensions 10.55 x 4.44 x 1.69 in. (268 x 113 x 43 mm)
Weight 0.62 lb (280 g)
Battery Type 9V
Battery Life 50 hours
Volume Flow Range 4 to 999,999 cfm
(FloRite 600)
Area Input Range 0.043 to 900 sq. ft (0.004 to 90 sq. m)
(Florite 600)
SPECIFICATIONS
PART NO. DESCRIPTION
16-7022 Florite 500 with Carrying Pouch
16-7023 Florite 600 with Carrying Pouch
16-0192 Airhood Kit*
Florite
®
500 & 600
Rotating Vane Air Velocity Instruments