Data Sheet
2012
p. 9/18
Attention!
Valves with flow direction above the seat are only conditionally usable for liquid media.
Waterhammer will occur! For flange and threaded port connections pilot pressures, please refer to Charts on page 8.
Control
function
Orifice
[mm]
Connection
Actuator
size Ø
[mm]
K
V
value
water
[m
3
/h]
Minimum
pilot pressure
[bar]
Operating
pressure up
to + 180 °C
[bar]
Article no.
PA actuator
Article no.
PPS actuator
A
Pneumatically
operated on / off
valve, normally
closed by spring
force, flow direc-
tion above seat
10 Flange 40 4.7
see charts
page 8
16
146427
–
Flange 50 4.7 16
146432
146492
15 Flange 40 4.7 16
146437
–
50 4.7 16
146443
146496
20 Flange 40 8.1 16
146448
–
50 8.1 16
146454
146500
25 Flange 50 13.0 16
146460
146504
32 Flange 63 19.5 16
146465
146508
40 Flange 80 31.0 16
146476
146512
50 Flange 80 45.0 16
146487
146516
65 Flange 125 73.0 10
152842
–
80 Flange 125 110.0 10
152851
–
100 Flange 125 165.0 6
152860
–
Control
function
Orifice
[mm]
Connection
Actuator
size Ø
[mm]
K
V
value
water
[m
3
/h]
Minimum
pilot pressure
[bar]
Operating
pressure up
to + 180 °C
[bar]
Article no.
PA actuator
Article no.
PPS actuator
A
Pneumatically
operated on / off
valve, normally
closed by spring
force, flow direc-
tion above seat
10 G ⅜ 40 4.7
see charts
page 8
16
146428
–
50 4.7 16
146433
146493
15 G ½ 40 4.7 16
146438
–
50 4.7 16
146444
146497
20 G ¾ 40 8.1 16
146449
–
50 8.1 16
146455
146501
25 G 1 50 13.0 16
146461
146505
32 G ¼ 63 19.5 16
146466
146509
40 G 1 ½ 80 31.0 16
146477
146513
50 G 2 80 45.0 16
146488
146517
65 G 2 ½ 125 65.0 10
152844
–
2 (A)
1 (P)
Valves with stainless steel body and flange connection according to DIN EN 1092-1, flow above seat
Valves with stainless steel body and threaded port connection, flow above seat
Ordering chart valves with flow direction above the seat (other versions on request)
Further versions on request
i
Port connections
Flange acc. to ANSI, JIS
Threaded port NPT, Rc
Clamp
Control function
I (double-acting actuator) and B (spring-return normally-open)
Approvals
GL, EC Gas Appliances Directive (previously DVGW), SIL
Mediums temperature
Valves for mediums temperature up to + 200 °C or down to - 40 °C
➔
2 (A)
1 (P)