Transmitter Cond Ind 7100e/2(X)
Installation and connection
Information on installation
Installation may only be carried out by trained experts in
accordance with this instruction manual and as per applicable
local and national codes.
Be sure to observe the technical specifications and input ratings.
Be sure not to notch the conductor when stripping the insulation.
When commissioning, a complete configuration must be
carried out by the system administrator.
Connection to supply units
Transmitter Cond Ind 7100e/2H: Before connecting this device
to a supply unit, make sure that its output voltage cannot exceed
30 V DC. Do not use alternating current or mains power supply!
Transmitter Cond Ind 7100e/2XH: This device may only be
connected to an explosion-proof power supply unit (for input
ratings refer to annex of EC-Type-Examination Certificate).
Terminals: suitable for single wires / flexible leads up to 2.5 mm
2
(AWG 14)
The connections to the transmitter must be installed
in accordance with the National Electric Code (ANSI-
NFPA 70) Division 2 hazardous (classified) location
non-incendive wiring techniques.
FM Control Drawing: Refer to page
Division 2 wiring
94.
Warning!
Additional safety precautions have to be taken for applications in
hazardous locations to CSA!
(See Pg 97 et seq.)