User Manual

Refer to the descriptions below to connect the other end of the AC power cord to the AC
distribution panel.
Do NOT plug the AC power cord into the wall socket prior to connecting ALL three AC power
wires to the rear panel and securely mount the safety metal housing over the input receptacle.
Doing so may create a shock hazard.
Connection of this power supply to an AC power source should be made by a qualified electrician
or other qualified personnel. Incorrect wiring may damage the power supply or cause a fire hazard
Connect the three terminals black to line1 (L1), white to line2 (L2) or neutral (N), and green to ground (G)
on the other end of the power cord to your AC distribution panel.
Figure 2.2
AC Power Cord
Safety agency requirements dictate that there must be a way to physically
disconnect the AC mains cable from the unit. A disconnect device, either a
switch or circuit breaker must be meet the input rating requirements at 30A
in 200 Vac. The disconnect device provided in the final installation must be
close to the instrument, must be easily accessible, and must be marked as
the disconnect device for this instrument.