WARNING: 
DO NOT output 10 A or more with only one pair of 
(+) and (-) terminals. Both (+) and (-) terminals 
must all be connected for applications requiring 
more than 10 A output. Each terminal can only 
accept a maximum of 10 A. Exceeding this may 
damage the power supply. 
Table 2- Wire Gauge Rating 
AWG 
10 
12 
14 
16 
18 
20 
22 
24 
26 
28 
Imax(A) 
40 
25 
20 
13 
10 
7 
5 
3.5 
2.5 
1.7 
mΩ/meter 
3.3 
5.2 
8.3 
13.2 
21 
33.5 
52.8 
84.3 
133.9 
212.9 
Rear Panel Output 
+S   
+  
+  
- 
- 
- 
S   
DUT 
+ - 
+S +  - -S 
Remove shorting bars 
Front Panel Output 
For 10 A or higher current output 