User Manual
50 
Disable (OFF) input: Disconnect the short between the two pins. 
Note: The external analog control does not have to be turned ON from the menu for 
these pins to function as intended. To avoid accidentally turning ON the load’s 
input, keep these pins opened with nothing connected when external On/Off 
control is not used or needed. 
Voltage Fault Indicator 
The terminal pin labeled VF in the rear panel outputs a 5 VDC signal under normal operations. 
When OVP, LRV, or RRV conditions occur, the pin will output 0 VDC to indicate the protection 
trip. 
Current Monitor 
The rear panel has a BNC output labeled I Monitor for current monitoring. It will output a 0-10 
V analog signal which reflects 0 - full range of the input current accordingly. You can connect an 
external voltmeter or an oscilloscope to display the input current’s change. 
3.5  Short Operation 
The electronic load can simulate a short circuit at its input. During front panel operation, press 
( ) and then   to switch the short on/off state. Short operation will not affect the 
present setting. When turning off the short state, the load returns to the original set state. 
The actual value of the electronic load in short operation depends on the mode and range that 
is active when the short is turned on. In CC or CR mode, the maximum short current is typically 
110% of the current range. In CV mode, short means setting the load’s constant voltage to be 0 
V. In short operation mode, you can measure the maximum short current (Amax) or DC current 
(ADC) of the power source to be measured. You can set this function via the Configuration 
menu. 










