Manual

Accessories
60
308
305
300
Type Analog Analog Analog Digital
Output Voltage 1000VDC 500VDC 1000VDC 1000VDC
Maximum current 250µA 500µA 2mA 1.2mA
Resistance Range 1M -2000M 0.2M - 1000 M 1000V 0-200M 0-2000M
500V 0-100M 0-2000M
250V 0-50M 0-2000M
Center Scale 50M 20M 1M, 2M, 4M Does not apply
Accuracy
Infinity: within 1% of scale length
Zero: within 1% of scale length
All points ±5% of reading
AC Voltage Test
Range 0 to 600 VDC Live Circuit Indicator
Frequency Response 10Hz to 100kHz
Accuracy ±4% of full scale
Low resistance Test Does not apply 0-50 0-200
Accuracy Does not apply ±5% of reading ±(1.5% + 2 digits)
General Specifications
Power Requirements Six “AA” cells (supplied) Eight “AA” cells (supplied)
Battery Life 4 hours typical alkaline 12 hours continuous 10 hours continuous w/alkaline
Operating Temperature 32˚ to 122˚F (0˚ to 50˚C), 70% RH
Storage Temperature -4˚ to 140˚F (-20˚ to 60˚C), <80% RH (with batteries removed)
Dimensions 6.66 x 4.18 x 1.42" (169 x 106 x 36mm) 7 x 8.5 x 3.5" (180 x 220 x 90mm)
Weight 15oz. (430g) w/batteries 2.6 lb (925g) with batteries
250V 500V 1000V
0-100 ±(1.5%+3D) ±(1.5%+2D) ±(1.5%+2D)
100-200M ±(2%+5D) ±(1.5%+2D) ±(1.5%+2D)
200-1700M ±(3%+7D) ±(3%+4D) ±(3%+3D)
1700-2000M ±(4%+8D) ±(4%+6D) ±(4%+5D)
Models 300, 305
These insulation testers are intended primarily for periodic testing of industrial
motors, transformers, electrical wiring, and cable insulation for signs of deteri-
oration. Low readings may indicate impending failure and permit replacement
during routine maintenance rather than risking production downtime. Also
useful for safety testing of TV sets and appliances to assure
no hazardous leakage current. The voltage and resistance ratings for insulation
testing are often specified for the product to be tested.
Supplied: Batteries, Carrying Case, Test Leads, Instruction Manual Batteries, Integral Carrying Case w/strap, Test Lead, Instruction Manual
Specifications
models
300 305 307 308
Models 307, 308
Selectable 250V, 500V, or 1000V insulation test
Low resistance test
Extra rugged integral carrying case
Live circuit indicator warns of safety hazard
Push to test
Test insulation resistance
Measure AC voltage to 600V
Battery powered
1000V, 2000M (Model 300)
500V, 1000M (Model 305)
One Year Warranty
307

Summary of content (1 pages)