Table 3.1: IS Series Utility Reference
Dimension IS-14120 IS-18120 IS-24120 IS-32120
inch mm inch mm inch mm inch mm
A 66 1676 71.57 1818 71.57 1818 79.5 2019
B 159 4039 159.84 4060 159.87 4061 159 4039
C 32.5 826 33.9 861 45.51 1156 62.5 1588
D 18.25 464 25.88 657 24.6 625 18.25 464
E 24.38 619 25 635 25 635 26.5 673
F 18 457 19.29 490 19.29 490 18 457
G 25 635 27.17 690 27.17 690 21.5 546
H 48 1219 49.75 1264 47.1 1196 48 1219
I 16 406 16 406 16 406 16 406
J 9.75 248 9.75 248 9.75 248 8.5 216
K 37.25 946 45.5 1156 41.93 1065 46.5 1181
ducing this clearance is not recommended. You must allow space around the machine for mainte-
nance.
3.3.2 Floor Requirements
The installation site must have flooring capable of supporting the weight of the machine with-
out flexing. Consult the general specifications in the previous section for specific details on the
machine’s weight and other technical specifications. No special foundation, grouting, or anchor-
ing is required by the manufacturer, but some shimming may be required so that the machine is
completely level. Always follow local codes when performing a machinery installation. It is the
responsibility of the installer to be familiar with the requirements of local codes.
3.3.3 Gas Requirements
The ironer requires a significant gas service capable of providing the volume and pressure needed
to achieve the BTU rating of the particular machine. Typical gas pressure ranges from 12 inches
water column to 2 PSI with ratings up to 825,000 BTU. Refer to the previous section for gas con-
nection sizing, gas pressure requirements and BTU ratings.
3.3.4 Exhaust Duct Requirements
A short run of exhaust vent ducting is required and must be procured locally. Adequate ventilation
is required and must meet all local codes. Refer to the previous section for airflows and other
11