User manual

OPERATION MANUAL
Technical changes reserved
0141 0316-192 13.08.2015
Pt1000 transducer module with
standard signal output
Connection layouts
Voltage output
Temperature measurement 0 ... 10 V, Type –10V
Identication: See picture
Pin Function Description
1 +DC 24 V Operating voltage
2 GND 0V Reference potential
3 TEMP 0 ... 10 V Temperature signal
0 ... 10 V
4 SHIELD Shielding (optionally)
The measurement of the output signal should be done with separate
signal ground, in order to avoid measuring error due to voltage drop
at the supply ground.
Sensor connection
Current output
Temp. measurement 4..20 mA,Type –20MA
Identication: See picture
Pin Function Description
1 +DC 24 V Operating voltage
2 TEMP 4 ... 20 mA Temp. signal 4 ...
20 mA
3 OWI dont use!
4 SHIELD Shielding (optionally)
The shielding (SHIELD) is to be optionally covered. Connection
through shielded cables is recommended.
Sensor connection