User manual

OPERATION MANUAL
Technical changes reserved
0141 0316-224 02.12.2014
Humidity-Temperature probe with
standard Signal FF-GLT-Series
Plug conguration
Humidity measurement 0 ... 10 V, without Temperature measurement,
Type –TE0
Pin Function Description
1 +DC/AC 24 V Operating voltage
2 GND 0 V Reference potential
3 HYGRO 0 ... 10 V Humidity Signal 0 ... 10 V
The measurement of the output signal should be done with separate
signal ground, in order to avoid measuring error due to voltage drop
at the supply ground.
Humidity measurement 0 ... 10 V and Temperature measurement
0 ... 10 V, Type –TE1
Pin Function Description
1 +DC/AC 24 V Operating voltage
2 GND 0 V Reference potential
3 HYGRO 0 ... 10 V Humidity-Signal 0 ... 10 V
4 TEMP 0 ... 10 V Temperature-Signal 0 ... 10 V
Temperature and humidity is always with reference to GND, operating
voltage +DC/AC 24 V is common for both transmitters.
The measurement of the output signal should be done with separate
signal ground, in order to avoid measuring error due to voltage drop
at the supply ground.
B+B Thermo-Technik GmbH | Heinrich-Hertz-Straße 4 | D-78166 Donaueschingen
Fon +49 771 83160 | Fax +49 771 831650 | info@bb-sensors.com | bb-sensors.com