Datasheet

DATA SHEET
Technical changes reserved
Humidity measurement 0 ... 10 V and passive Pt1000 for Tempera-
ture measurement, Type –TEPT
Pin Function Description
1 +DC/AC 24 V Operating voltage
2 GND 0 V Reference potential
3 HYGRO 0 ... 10 V Humidity-Signal 0 ... 10 V
4 --- Unoccupied
5 Pt1000 Temperature sensor (passive)
6 Pt1000 Temperature sensor (passive)
The Pt1000 is with brought out potential free with 3 wire connection.
The line resistance is to be compensated. Other types of measur-
ingresistances,forexample,NTCresistance,arealsopossible,if
required!
The measurement of the output signal should be done with separate
signal ground, in order to avoid measuring error due to voltage drop
at the supply ground.
Humidity measurement 4 ... 20 mA, without Temperature
measurement Type –TE0
Pin Function Description
1 +DC 24 V Operating voltage
2 HYGRO 4 ... 20 mA Humidity-Signal 4 ... 20 mA
3 --- Unoccupied
4 SHIELD Shielding
The shielding (SHIELD) is to be optionally covered. Connection
through shielded lines is recommended.
Humidity-Temperature probe with
standard Signal FF-GLT-Series
B+B Thermo-Technik GmbH | Heinrich-Hertz-Straße 4 | D-78166 Donaueschingen
Fon+4977183160|Fax+49771831650|info@bb-sensors.com|bb-sensors.com
5 / 7