User manual
OPERATION MANUAL
Technical changes reserved
0141 0316-214 17.08.2015
Industrial pressure transmitter with
voltage or current output - DRTR-ED-XX-R
Connection layout
Pin Voltage output Current output
1 +DC 12…30 V +DC 10…30 V
2 GND 0 V I PRESSURE 4…20 mA
3 U PRESSURE 0…10V ---
4 SHIELD SHIELD
Connection diagramm
Current output 4...20 mA
Voltage output 0...10 V
Dimensions
Delivery spectrum
Measuring range Bursting pressure Ordering No. for current output Ordering No. for voltage output
-1…0 bar 4 bar DRTR-ED-20MA-RV0 DRTR-ED-10V-RV0
-1…1 bar 4 bar DRTR-ED-20MA-RV1 DRTR-ED-10V-RV1
0…1,6 bar 4 bar DRTR-ED-20MA-R1B6 DRTR-ED-10V-R1B6
0…2,5 bar 6,25 bar DRTR-ED-20MA-R2B5 DRTR-ED-10V-R2B5
0…4 bar 10 bar DRTR-ED-20MA-R4B DRTR-ED-10V-R4B
0…6 bar 15 bar DRTR-ED-20MA-R6B DRTR-ED-10V-R6B
0…10 bar 25 bar DRTR-ED-20MA-R10B DRTR-ED-10V-R10B
0…16 bar 40 bar DRTR-ED-20MA-R16B DRTR-ED-10V-R16B
0…25 bar 62,5 bar DRTR-ED-20MA-R25B DRTR-ED-10V-R25B
0…40 bar 100 bar DRTR-ED-20MA-R40B DRTR-ED-10V-R40B
0…60 bar 150 bar DRTR-ED-20MA-R60B DRTR-ED-10V-R60B
0…100 bar 175 bar DRTR-ED-20MA-R100B DRTR-ED-10V-R100B
The relative pressure measurement, 0 bar corresponds to atmospheric pressure!
For more information visit our website please:
www.bb-sensors.com
B+B Thermo-Technik GmbH | Heinrich-Hertz-Straße 4 | D-78166 Donaueschingen
Fon +49 771 83160 | Fax +49 771 8316-50 | info@bb-sensors.com | bb-sensors.com
2 / 2