Instructions

OPERATION MANUAL
Technical changes reserved
0141 0316-212 20.04.2016
Rain Detector REGME
model 12 V AC/DC or 24 V AC/DC
DescriptionDescription
Technical Data
Measurement method Electrolytic AC measurements
Input current
12 V Model
24 V Model
60 mA, Heater 80 - 300 mA (PTC)
50 mA, Heater 40 - 180 mA (PTC)
CE-Conformance 2014/30/EU
EMV-noise emission EN 61000-6-3:2011
EMV-noise withstanding EN 61000-6-1:2007
Cable gland M16 x 1,5
Operating voltage
chooseable:
12 V AC/DC ± 10%
24 V AC/DC ± 10%
Output output (relay) 30 V / 4 A,
NO / NC selectable
Housing ABS, ingress protection IP54
Dimensions (w x h x d) 80 x 82 x 58 mm
Article Art.-No.
Rain Detector 12 V REGME-12V
Rain Detector 24 V REGME-24V
Combined wall/mast
mounting bracket
REGME-WAHA
Features
Safe operation, electrolytic measurement principle
Deposition can be detected as rain or snow
Operating voltage 12 or 24 V DC/AC
Large, heated sensor area for fast drying and operation in winter
season
Potential free contact output (Relay) 30 V/4 A
Sensitivity and switching mode adjustable
Universal wall/mast mounting bracket as accessories
Applications
Nurseries, Agriculture
Control of Ventilation panels
Automatic switch for Blinds and Rolling windows
Building instrumentation
Weather stations
Functional description
The large sensor area reacts to rain or snow. The switch polarity and
sensitivity are adjustable. The optionally switched heater prevents
freezing or dew formation and accelerates drying. In the maximum
sensitivity setting, the device is also suitable for recognizing fog.
Application
The rain guard is tted with a relay contact for switching low voltages
up to 30 V DC/AC which can be used to operate any switching device
e.g. a marking control device. Sensitivity can be adjusted within a wide
range. The device is provided with a heater for faster drying and snow
recognition.
Mounting
Installation of the rain sensor unit should be carried out by only
Authorised personnel. The applicable safety regulations should be
followed ! The Rain Sensor can be installed on a wall/mast mounting
bracket. If such accessories are not used, care should be taken that
the mounting angle is approximately 30 ° from horizontal. The points
of sensor area must be on the down side. Mounting of the Rain Sensor
should be done at a place which is freely accessible for rain. Dripping
water can adversely delay switching back or can lead to a permanent
ON/OFF of the contacts.
B+B Thermo-Technik GmbH | Heinrich-Hertz-Straße 4 | D-78166 Donaueschingen
Fon +49 771 83160 | Fax +49 771 831650 | info@bb-sensors.com | bb-sensors.com
1 / 2