User Manual

OP10 HMI
Part Number Description Price
OP10
4.3" Monochrome Graphic Panel, 192 x 64 pixels, 4 Function Keys, Numeric
Keypad, 2 serial ports, 24VDC input power
$129
OP10-PL01 Cable (9-pin Serial, PC to 9-pin Serial, OP10)
$19
SG2-PL01 SG2 to OP10 Communication Cable
$19
SG2-Software SG2 & OP10 Programming S/W. Available on CD or FREE via download.
$9
General Specications
Power DC24V, -15% ~ +10%
Current Consumption 80mA Max
Approvals UL, CE
Communication Interface COM1: (9-pin, D-SUB, female) RS-232/422; RS485: terminal screws
Environmental Rating IP65 (front of panel)
Maximum Devices 8 without repeater; 255 with repeater
Dimensions 179.5 x 101.5 x 33mm (7.07 x 4.00 x 1.30”)
Weight 460g (~1 lb)
Environmental
Operating Temperature 0°C ~ 55°C (32°F ~ 131°F)
Storage Temperature -40°C ~ 70°C (-40°F ~ 158°F)
Relative Humidity 10% ~ 95%, non-condensing
Vibration 1.75mm displacement, 5 - 9Hz
Impact 15G, 11ms, vertical from X, Y, Z directions
179.5mm (7.07”)
5.5mm
(0.22”)
33mm
(1.30”)
101.5mm (4.00”)
163.8mm (6.45”)
85.8mm
(3.38”)
Dimensions
The TECO OP10 monochrome HMI oers a simple but
powerful user interface for the SG2 (Ver 3) programmable
Logic Relay. Monitor data registers in real time, change
parameters, perform switching functions, list alarms, and
transfer data between networked SG2’s*.
• 192 x 64 pixel display
• 24-key keypad
• Two serial ports:
– COM1 supports programming and
point-to-point communications
– RS485 supports multi-drop
networks
• Supports Modbus RTU
• Password protection
• Import bitmaps
• Oine program simulation
• Bar graphs, trend charts, alarm
logging
Cutout
F R E E
Programming Software
Program the OP10 using simple ll-in-the-blank object windows.
Establish network links to remote devices. Create dynamic text, trend
charts, bargraphs, alarm logs, and more. View and verify your program
in simulation mode.
Download software free at:
www.bb-elec.com/bb-elec/software/PLC/OP10-PCLINKV2.1setup.exe
Multi-drop Modbus communications over RS485 network
Communication with one SG2 via programming port
NEW!
$
129
Dynamic Text
Trending
Bar Graphs
Simulation
Simple Setup
SG2-PL01
*SG2 must be V-series to communicate on RS485.
*
International Headquarters: 7 07 D a yto n R o ad P O B ox 1 040 O tta w a , IL 613 50 U S A
815-4 33-510 0 F a x 433 -5104 www.bb-elec.com order s @bb-elec.com support@bb-elec.com
European Headquarters: W e stlink C om m e rc ial P a rk O ra nm ore C o. G alw a y Irela nd
+35 3 9 1 792 444 F ax +35 3 91 79 2 44 5
www.bb-europe.com orders@b b-europe.com support@bb-europe.com