Figure 3-1-8. Declaration files have been added into this project.
Put a “CommandButton” control on Form1” of this program. Add the
following codes in the sub routine “Command1_Click() “ :
Private Sub Command1_Click()
Dim wt As Integer
Port = 2
Open_Com Port, 9600, 8, 0, 0
SendTo7000 = "$01M"
ReceiveFrom7000 = Space(100)
Send_Receive_Cmd Port, SendTo7000, ReceiveFrom7000, 100, 0, wt
Command1.Caption = ReceiveFrom7000
Close_Com Port
End Sub
Run the program and click on the “Command1” button. The caption of the
Command1” button will be changed to “!01xxxx”. The “!” is “OK”. The “01”
means “address at 0x01”. The “xxxx” is the module-ID. Refer to Figure 3-1-
9.
Figure 3-1-9. The module returns “!01xxxx”.