User Guide

40
I-7011, I-7018 User Manual Rev:B1.0
2.19 ~AAO(Data)
Description : Set Module Name
Syntax : ~AAO(Data)[CHK](cr)
~ delimiter character
AA address of setting module (00 to FF)
O command for setting module name
(Data) new name for module, max 6 characters
Response : Valid Command : !AA[CHK](cr)
Invalid Command : ?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
! delimiter for valid command
? delimiter for invalid command
AA address of response module(00 to FF)
Example :
Command : ~01O7018 Receive : !01
Set address 01 module name to 7018, return success.
Command : $01M Receive : !017018
Read address 01 module name, return 7018.
Related Command :
Sec.2.17 $AAM