User Guide

37
I-7011, I-7018 User ManualRev:B1.0
2.16 $AAF
Description : Read Firmware Version
Syntax : $AAF[CHK](cr)
$ delimiter character
AA address of reading module (00 to FF)
F command for reading firmware version
Response : Valid Command : !AA(Data)[CHK](cr)
Invalid Command : ?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
! delimiter for valid command
? delimiter for invalid command
AA address of response module(00 to FF)
(Data) firmware version of module
Example :
Command : $01F Receive : !01A2.0
Read address 01 firmware version, return version A2.0.
Command : $02F Receive : !01B1.1
Read address 02 firmware version, return version B1.1.