User Manual
SPECIFICATION
MODEL
MTBF
DIMENSION
NOTE
PACKING
1. All parameters NOT specially mentioned are measured at rated load and 25 of ambient temperature.
2. Every 25 seconds, unit will send out test signal through "Battery Fail" relay contact and LED indicator once the battery is fail.
FileName:DR-UPS40-SPEC2007-04-02
40A DCUPSModule
DR-UPS40
Features :
DCINPUT/
DCBUS
BATTERY
INPUT/
OUTPUT
OTHERS
ENVIRONMENT
DR-UPS40
DCVOLTAGE(Typ.)
RATEDCURRENT
VOLTAGERANGE(Typ.)
CURRENTRANGE
CHARGECURRENT(Typ.)
EXTERNAL BATTERY (Typ.)
RELAY CONTACTRATING(max.)
DCBUSOK
BATTERY FAIL Note.2
BATTERY DISCHARGE
WORKINGTEMP.
WORKINGHUMIDITY
STORAGETEMP.,HUMIDITY
VIBRATION
24~29V
40A
21~29V
0~40A
2A
4/7/12AH/24V
30VDC,1A
Relaycontact:ShortwhenDCvoltagebetween21~29V( 3%),relaycontacts
LED(Green):DCBUSOK:light;DCBUSfail:dark
Relaycontact: Shortwhenbatteryfailureisobservedthroughthebatterytestfunction,relaycontacts
LED(Red):Batteryover-dischargewarningorbatterybroken:light;BatteryOK:dark
Relaycontact: Shortwhenbatteryindischargecondition,relaycontacts
LED(Yellow):Batterydischarging:light;Batteryisnotdischargingordischargingcurrent<2.0A :dark
-20~+70
20~90%RH
-20~+85 ,10~95%RH
Component:10~500Hz,2G10min./1cycle,60min.eachX, Y,Zaxes;Mounting:CompliancetoIEC600068-2-6
FUNCTION
161.9Khrsmin.MIL-HDBK-217F(25 )
55.5*125.2*100mm(W*H*D)
0.55Kg;20pcs/12Kg/1.1CUFT
SAFETY &
EMC
Battery controller for DIN Rail UPS system
Parallel connection to DC BUS
Suitable for 24V system up to 40A
Installed on DIN Rail TS35 / 7.5 or 15
Built-in battery test function
Battery polarity protection
Relay contact signal output and LED indicator for DC BUS OK,
Battery Fail, and Battery Discharge
Cooling by free air convection
3 years warranty
WITHSTANDVOLTAGE
ISOLATIONRESISTANCE
Terminal-Chassis:>100MOhms/500VDC25 70%RH
Terminal-Chassis:0.5KVAC,RelayContacts-Terminal:0.5KVAC
EMSIMMUNITY
EMICONDUCTION&RADIATION
CompliancetoEN55022(CISPR22)ClassB
CompliancetoEN61000-4-2,3,4,5,6,8,ENV50204,heavyindustrylevel,criteria A