Owner's manual
SETTING THE CONTROLS
Program Mode:
General Note:
!
!
!
Press and hold the Key or Key to change the value continuously (auto repeat function).
To return to normal operating mode from the program mode, press and hold the key for 3 seconds. However, the system also return to normal operating
mode if no key is pressed for 30 seconds.
During the program mode, each time key is pressed, the data will be saved into the EEPROM and advance to the next setting(parameter). If no change of
value is required, just press key once to go to the next step (parameter).
Up Down
SET
SET
SET
Steps
Step1
Step 2
Step 3
Step 4
Step 5
Procedures
SET
FC
Up Down F C
SET
S1
Up Down
SET
dF1
Up Down
SET
H1
C1 Up Down
C1 H1
SET
AC1 Up Down
SET
To start programming, press the key for 3 seconds to access the
Fahrenheit/Celsius mode. The lower LCD display will show the current status,
either for degrees Fahrenheit or for degrees Celsius. This annunciator will be
flashing. Then press either or key to toggle between the or scales.
Press key again to access the stage 1 setpoint mode. The lower LCD will
display the current setpoint (flashing) and the upper LCD will display
annunciator. Then press either the key to increase or the key to
decrease the setpoint to the desired setting.
** Please note that this value as well as all the temperature related value are
in degree Fahrenheit as set in step 1.
Press key again to access the stage 1 differential mode. The lower LCD will
display the current differential (blinking) and the upper LCD will display
annunciator. Then press either the key to increase or the key to
decrease the differential to the desired setting.
Press key again to access the stage 1 heating or cooling mode. The upper
LCD will display the current mode, with flashing annunciator, either for
heating or for cooling. Then press either the key or the key to toggle
between the or operation.
Press key again to access the stage 1 Anti-Short Cycle time delay. The
lower LCD will display the current time delay(blinking), in minute and the upper
LCD will display . Then press either the key to increase or the key
to decrease the delay to the desired setting. The increment is in 1 minute. Press
key again to go back to normal operating mode.
Description
Fahrenheit or Celsius Scale
Stage 1 Setpoint
Temperature
Stage 1 Differential
Temperature
Stage 1 Heating or Cooling
Stage 1 Anti-Short Cycle
time delay
The default value is
Default setting is:
Default setting is:
Default setting is:
Default is: minutes
F
75F
1F
H1
0
LCD Display
0
75f
Si
8f i
If
Hi
Ac i
93
Down Key
Up Key
Reset Key
Backlit Switch
2 Setpoint
Temperature for
1 Sensor Input or
Sensor 2 Temperature
for 2 Sensor Input
Sensor 1
Temperature
Fuse
Relay Output
Status
Indicator LED
SET Key
WIRING THE CONTROL
Refer to Figure 3 for
typical wiring
connections. Do not use
wire larger than 12 AWG
as jumper between
terminal blocks (eg.
“120V” and “C”)
Programming Steps
POWER ON
All the slide switches (Backlit and Sensor Inputs) should be set before the control is powered up (so the desired switch settings are scanned by the
microprocessor). However if the settings on the slide switches are changed after power is supplied, press the key so that the switch settings can be
updated.
When the control is powered up, the model ID - “2SP” is displayed. Then the control will run Anti-short cycle delay(if any) and goes into normal operating mode.
If 1 sensor input is selected, the Upper LCD will display the current sensor 1 temperature and the Lower LCD will display the two setpoint temperature
alternatively.
If 2 sensor input is selected, the Upper LCD will display the current sensor 1 temperature and the Lower LCD will display current sensor 2 temperature.
RESET
!
!
Figure 3: Typical Wiring Diagram for DST-7772
with 120Vac Load
Terminal Representations:
RELAY 1/RELAY 2
SENSOR INPUT
240V is the hot of the 240Vac line voltage
COM is the neutral or ground of the line voltage
120V is the hot of the 120Vac line voltage
NC is Normally Close of SPDT switch and opens when
the relay is energized
C is Common of the SPDT switch
NO is Normally Open of the SPDT switch and closes
when the relay is energized
S1 S1 are the input terminals for sensor probe P-01for
controlling relay 1by Stage 1 setpoint.
S2 S2 are the input terminals for sensor probe P-01for
controlling relay 2 by Stage 2 setpoint.
S2 S2
SENSOR
INPUTS
2
1
240V COM 120V
RELAY 1
NOCNC
SENSOR INPUTS
AC INPUT
120 VAC
(HOT)
(COM)
LOAD
SENSOR
PROBE
(P-01)
RELAY 2
NOCNC
LOAD
Checkout
! Before power is applied to the
control, make sure that the
installation and wiring
connections are done correctly.
Also, ensure that the wires
connecting to COM and 120V
are not touching each other.
! Ensure that wires of the senor
probe are not touching each
other
S1 S1
2
2