Owner manual
AZELAZEL
TECHNOLOGIES
SZ-84/86DX
MULTI- ZONE ZONE VALVE CONTROL
INSTALLATION AND OPERATING INSTRUCTIONS
FEATURES
.
.
.
.
.
.
.
.
.
.
Front panel indicator lights
Field selectable Priority
Priority timer for protection of a priority zone malfunction
and prevention of freeze-ups in the heating zones
Unlimited zone expansion
Dual Isolated End Switches
Three-minute End Switch delay timer for two wire type
zone valve applications. Circulator will start only after
the zone valve is fully opened.
DIP switch for easy setup of two wire type zone valve
applications. No need to hook up wire jumper on the
third and fourth terminals on each zone
Works with two, three or four wire type zone valves and
thermostats
Compact and modern design
Fuse protection
.
.
.
.
.
.
.
.
Safety design with all electronic components hiding
behind the enclosure
Simplified wiring
Contractor friendly PCB layout
Easy-Connect Screwless Terminals
24VAC transformer output with common terminal
provides compatibility with electronic thermostats
Universal thermostat compatibility
100% Factory Tested
Extended three year warranty
APPLICATION
The series multi-zone zone valve controller is
operated by low voltage thermostats or any other low
voltage controllers having an SPST switching action.
The -Link controller provides intermediate switching to
permit up to six zone valves and a boiler operating control
in a multi-zone hydronic heating system.
Intelligent Linking System ( -Link) allows unlimited zone
expansion with additional -Link controllers.
The panel provides EZ screwless terminal blocks for
connections to the thermostats. LED indicators on the front
panel provides functional status and easy troubleshooting.
i-Link
i
i
i
Field
selectable priority with protection timer prevents freeze-
ups in the event of a priority zone failure. The three-minute
delay timer let the two wire type zone valve fully open
before turning on the circulator.
MOUNTING
Mount the Link controller to a suitable surface. Slotted
keyholes and standard holes are provided for mounting
purposes.
i-
ROUGH-IN WIRING
Loosen the screws on the top and bottom of the enclosure
and remove the wiring covers by swinging them away from
the base(grey color) with the edges of the covers as pivot(see
Figure 1).
The base has standard 7/8” (22mm) knockouts which accept
common wiring hardware and conduit fittings. Before
removing the knockouts, check the wiring diagrams and use
the chamber with common voltages.
SPECIFICATIONS
Model: SZ-84DX 4 Zone Valve Control
SZ-86DX 6 Zone Valve Control
Power Supply: 24 VAC, 50/60Hz
Dimensions: 6 3/8”(W) x 6 5/8”(H) x 2 3/4”(D)
Electrical Switch Rating: 10 A 1/3 HP @ 120VAC
Thermostat Anticipator Setting: 0.18 A
Enclosure: Flame Retardant Plastic 94V0
Shipping Weight: 3 lbs.
CAUTION!
1. To prevent electrical shock hazard, disconnect power supply
before installing.
2. All wiring must comply with national and local electrical codes,
ordinances, and regulations.
Never connect the load terminals to a load that takes more
current than the amount listed for the relay in the electrical
ratings.
3. Azel Technologies is not responsible for damages resulting from
misuse of its products.
4. 12-22 gauge wire is recommended for thermostat connections.
5. This literature is provided for informational purposes only.