Service manual
(1) Compressor frequency control 
According to difference room temperature and set temperature(¥t = RT-ST), running 
frequency of compressor is controlled by electronic controller. When room temperature is much 
higher than set temperature, compressor will start at a high frequency, and as room temperature 
goes down, compressor running frequency will go 
down. When room temperature is lower than set 
temperature, compressor will run at very low frequency. In general, unit will change its running 
frequency according to¥t to make room temperature closing to set temperature.
(2)  Outdoor temperature affects running frequency of compressor 
Outdoor temperature affect compressor’s running frequency
. Difference inlet temperature of 
outdoor unit is adapted by difference compressor running frequency. While outdoor temperature is 
about 30ć, the compressor will run in high frequency.   
    If unit run in “cooling” mode and outdoor temperature is less than -1ćcontroller will shut down 
compressor and show error code, while the ambient temperature is over 0ć the compressor will 
run automatically
(3)  Auto fan control in cooling mode 
   In cooling mode (include cooling in “I feel” mode), fan speed is determined by ¥t, as the 
following diagram:   
ć
įt come down
high fan
įt come up
medium fan
low fan
RT-ST
4. “DRY” Mode Operation 
(1) The system for DRY operation used the same refrigerant circle as the cooling one. 
(2) When the system operates in DRY mode, at first it operates in cooling mode at 16ć or 
18ć for 3 minutes. After that, the system will operate in cooling mode with lowest fan 
speed, meanwhile the set temperature (ST) is “RT-2ć” which means that the ST is room 
temperature at then minus 2. During the course of this mode, the fan speed set operation 
and room temperature set are restricted, except the vane motor adjusting.
5.    “HEATING” Mode Operation (available for Heat Pump only) 
(1) Frequency control 
The same as the frequency control in cooing mode, running frequency of compressor is 
controlled by controller. Unit change its running frequency according to  ¥t to make room 
temperature closing to the set temperature.
(2)  Indoor fan motor control 
1. Cold Air Prevention C
ontrol
z  The function is intended to prevent cold air from being discharged when the heating 
operation starts or when defrosting. 
z  The indoor fan speed will be controlled as following. 
Service Manual • T-series Ducted Air Conditioner
Page 8