User`s manual
Chapter 4 Serial Communications AX2200/AX2300 Instruction Manual
4-26 CM2-AX2000-2001 (Rev. 4, 4/2014)
protocol‐object‐types‐
supported
{T,F,F,T,F,T,F,F,T,F,F,F,F,F,F,F,F,F,F,F,F,F,F,F,F}
object‐list {(analog‐input,1),(analog‐input,2),(analog‐input,3),(analog‐input,4),
(analog‐input,5),(analog‐input,6),(analog‐input,7),(analog‐input,8)
(analog‐input,9),(analog‐input,10),(analog‐input,11),(analog‐
input,12),(analog‐input,13),(analog‐input,14),(analog‐
input,15),(analog‐input,16),(analog‐input,17),(analog‐
input,18),(analog‐input,19),(binary‐input,1),(binary‐input,2),(binary‐
input,3),(binary‐input,4),(binary‐value,1),(device,7)}
max‐apdu‐length‐
accepted
300
segmentation‐supported no‐segmentation
apdu‐timeout 3000
number‐of‐APDU‐retries 1
max‐master 127
max‐info‐frames 1
device‐address‐binding ()
database‐revision 0
Note‐DeviceCommunicationControl:Password–“
azbil
”
3.2. AnalogInputObject:
Vortex Mass Flow Meters Analog Input type objects are described
in the below Table –
ObjectInstance ObjectName Unit Description
1 VolumeFlow cubic‐feet‐per‐second,
cubic‐feet‐per‐minute,
us‐gallons‐per‐minute,
imperial‐gallons‐per‐
minute,
liters‐per‐minute,
liters‐per‐second,
liters‐per‐hour,
cubic‐meters‐per‐second,
cubic‐meters‐per‐minute,
cubic‐meters‐per‐hour
ThisAIobjectisusedto
measurevolumeflow.
2 MassFlow pounds‐mass‐per‐second,
grams‐per‐second,
kilograms‐per‐second,
kilograms‐per‐minute,
kilograms‐per‐hour,
pounds‐mass‐per‐minute,
ThisAIobjectisusedto
measuremassflow.