AX2200/AX2300 Instruction Manual Chapter 2 Installation
CM2-AX2000-2001 (Rev. 4, 4/2014) 2-23
Frequency Output Connections
The frequency output is used for a remote counter. It can be scaled to out-
put a 1 to 10 kHz signal proportional to mass or volume flow, tempera-
ture, pressure or density.
The frequency output requires a separate 5 to 36 VDC power supply;
however, there are current and power specifications that must be ob-
served. The output can conduct a current up to 40 mA and can dissipate
up to 200 mW. The output is isolated from the meter electronics and pow-
er supply.
Figure 2-19. Isolated Frequency Output Using External Power Supply
Figure 2-20. Non-Isolated Frequency Output Using External Power Supply
Optional Backlight Connection
The loop power meter has an optional backlight connection provided. It is
intended to be powered by a separate 12 to 36 VDC at 35 mA max. power
supply or by the pulse power input. Both options are shown below.
F
igure 2-21.Backlight Using External Power Supply