Specifications
www.baldormotion.com
Input / Output 4-9MN1941
4.3.1.4 Typical digital input wiring
NextMove e100
8
9
DIN4
CREF1
TLP281
User
supply
GND
User
supply
24 V
‘X9’
6k2100R
Figure 11 - Digital input - typical ‘active high’ input connection using a switch
NextMove e100
8
9
DIN4
CREF1
TLP281
User
supply
GND
User
supply
24 V
‘X9’
6k2100R
Figure 12 - Digital input - typical ‘active low’ input connection using a switch
Note: The circuits shown in Figures 11 and 12 are not suitable for use with fast inputs DIN0
to DIN3. Using a mechanical switch, relay contacts or other source liable to signal
‘bounce’ could cause unwanted multiple triggering.
NextMove e100
Status+
Status-
8
9
MicroFlex e100 /
equipment output
DIN4
CREF1
TLP 127
TLP281
User
supply
GND
User
supply
24 V
11
1
‘X9’
‘X3’
6k2100R
Figure 13 - Digital input - typical connections from a Baldor MicroFlex e100