Technical data
II.3 Commissioning
The commissioning of servo amplifiers can only be carried out by qualified personnel
with extensive knowledge of the fields of electrical engineering and drive technology.
The method of commissioning is described in an example. A different method may be appro
-
priate or necessary, depending on the usage of the equipment.
In the case of multi-axis systems, each amplifier must be commissioned individually.
Page II - 14 Installation and commissioning Chapter II
01.98 digifas™ 7100 series
Caution !
Check that all live connection components are protected against accidental contact.
Dangerous voltages can occur up to 750V.
Never disconnect the electrical connections of a servo amplifier which is live.
The residual charge in the capacitors can still have a dangerous level up to 120 seconds
after the mains supply has been switched off.
The amplifier heat sink can reach a temperature of 80°C in operation. Check (measure)
the temperature of the heat sink. Wait until it has cooled down to 40°C before touching
it.
Further information on commissioning :
The adjustment of parameters and the resulting effects on the control characteristic are
described in the operating manual for the operator software BS7200.
The commissioning of the CONNECT modules is described in the corresponding
manual.
More detailed knowledge can be acquired through our training courses (on request).
Caution !
If the servo amplifier has been stored for longer than 1 year, the DC-link capacitors
must be re-formed.
In this case, undo all the electrical connections.
Feed the servo amplifier for about 30min from single-phase 230V AC to the terminals
L1 / L2. The capacitors will then be re-formed.