192 Rockwell Automation Publication MOTION-UM003F-EN-P - March 2015
Chapter 8 Home an Axis
Online Scaling
Any change or SSV message that results in a motion resolution change can
generate an APR fault.
Resetting an APR Fault
There are three ways to reset an APR Fault:
Instruction execution:
Executing an MAFR
Executing an MGSR
Executing an MASR
Executing a MCSR
Do the following from the Controller Organizer:
Clear the group fault, the software executes an MGSR
Clear the axis fault, the software executes an MASR
Download the same project a second time
Absolute Position Loss without APR Faults
The Absolute Position Recovery is not retained after the following:
A project is exported, saved as a .L5K, and imported (downloaded)
A major non-recoverable fault (MNRF)