Chapter 7 Commission
Troubleshoot the Safe Torque Off Function
For complete information about troubleshooting the Safe Torque Off function,
see the Kinetix 5500 Servo Drives User Manual, publication 2198-UM001
and
the Kinetix 5700 Multi-axis Servo Drives User Manual,
publication2198-UM002
.
K5500ers2 STO Networked .SafetyStatus Logix K5500ers2 Profile, and Module-Defined tag.
K5700 STO Hardwired .GuardStatus None (Hardwired)
K5700 STO Networked .SafetyStatus Logix K5700ers2 Profile, K5700 is two pieces of
functionality in 1 hardware package and Module-
Defined tag.
Table 19 - Drives Supporting STO - Safe Torque Off
Drive Mechanism Axis Status STO Configuration
Table 20 - 2198-Hxxx-ERS2 Servo Drive Troubleshooting
Exception Code on Drive Display
Fault Message
Logix Designer
Problem Possible Solutions
SAFE FLT S01- Safety Core Internal CPUWatchdogFault
(1)
Drive safety diagnostic detected internal STO design failure.
Cycle control power
Return drive for repair if fault continues
SAFE FLT S03- Safe Torque Off SafeTorqueOffFault
(2)
Drive safety diagnostic detected internal STO design failure.
Cycle control power
Execute STO function
Return drive for repair if fault continues
(1) Displayed in the Quick View Pane as Module Fault.
(2) Displayed in the Quick View Pane as Safety Fault.