User manual

162 Rockwell Automation Publication MOTION-UM003F-EN-P - March 2015
Chapter 7 Commission
3. Set the Speed to the expected operation speed.
4. Set the Torque to the level you want to apply to the motor during the
Autotune.
The default of 100% Rated Torque usually give good results.
5. Set the Direction that is based on machine constrains.
Unidirectional tune profile measures inertia and friction. Bidirectional
tune profile adds measurement of active torque loading.
6. Click Start.
This message appears if you have edits that have not been applied. If you
dont save pending edits, Autotune does not run.
The Autotune status should display Success. A tune configuration fault
can occur if any number of attributes are zero.
The Autotune profile accelerates and decelerates the motor according to
the Tune Direction.
TIP
Blue arrows next to a field means that these values are immediately
applied. Once you put a value in the field and then leave that field, it is
automatically sent to the controller.
Fault Description
Tune Configuration Fault A tune configuration fault can occur if any number of
attributes are zero. This occurs only when you use Nameplate
Data as the motor data source. The following attributes are
checked for zero:
Tuning Torque
Conversion Constant
Drive Model Time Constant
System Damping (Damping Factor)
Rotary Motor Inertia
Linear Motor Mass
The Kinetix 350 drive does not support this attribute.
Motor Rated Continuous Current
PM Motor Rotary Voltage Constant
PM Motor Linear Voltage Constant
Rotary Motor Rated Speed
Linear Motor Rated Speed