Technical data

Regen Resistor Model Resistance Rated Power Drives SEC-SDDR8/14-SA Drives SEC-SDDR14/24-SA
[] [Watts] SEC-SDDE8/14-SA SEC-SDDE14/24-SA
SEC-SDD-RR-55 50 55
SEC-SDD-RR-95 40 95
SEC-SDD-RR-230 81 230
SEC-SDD-RR-650 72 648
SEC-SDD-RR-700 54 700
SEC-SDD-RR-845 40 845
12/2006 – Subject to change – Multi-Axis Controllers and ServoWire
®
Digital Drives
39
Regen Resistor/Drive Compatibility and Line Filter Selection and Sizing
Engineering Support
4
Regen Resistor/Drive Compatibility
Key
* Compatible
** Peak Regen capacity of the drive
*** Limited by the resistor
Line Filter Sizing and Selection Recommendations
SEC-SDD Mains Power Drive Rated Line Filter Continuous Rated Power
ServoWire Drive Output Power kVA Current @ 230 VAC kVA @ 230 VAC
SEC-SDDR2/4-SA 115 VAC, 1 Ph 0.29 SEC-SDD-LF15 Up to 15 A 3.45
SEC-SDDE2/4-SA 230 VAC, 1 Ph 0.59 [1 Ph]
SEC-SDDR4/7-SA 115 VAC, 1 Ph 0.49 SEC-SDD-LF30 Up to 30 A 6.90
SEC-SDDE4/7-SA 230 VAC, 1 Ph 0.98 [1 Ph]
SEC-SDDR8/14-SA 115 VAC, 1 Ph 0.58 SEC-SDD-LF30X Up to 30 A 11.70
SEC-SDDE8/14-SA 230 VAC, 1 Ph 1.17 [3 Ph]
230 VAC, 3 Ph 1.95
SEC-SDDR14/24-SA 115 VAC, 1 Ph 0.98 SEC-SDD-LF30X Up to 30 A 11.70
SEC-SDDE14/24-SA 230 VAC, 1 Ph 1.97 [3 Ph]
230 VAC, 3 Ph 3.32
A three-axis system comprising of two SEC-SDDR2/4-SA drives and one SEC-SDDR8/14-SA drive, all operating on 115 VAC single-phase.
Line filter required: One SEC-SDD-LF15
[0.29 x 2 + 0.58 = 1.16 kVA]
In the case of a system using multiple SEC-SDD ServoWire drives, they may share one line filter per cabinet. When selecting the line filter size,
the fact that all drives/motors will not be operating at the same time needs to be taken into account.
Suitable for typical point-to-point motion
Suitable for continuous regenerative and overhauling loads
*
**
***
*
**
***
*
*
*
N/A
*
N/A
Drive Line Filter
System Examples
Example #1
Example #2
An eight-axis system comprising of eight SEC-SDDR14/24-SA drives operating on 230 VAC, three-phase.
Line filter required: SEC-SDD-LF30X (one filter would be required if 4 drives are operating at a time).
[3.32 x 8 x 1.7321 = 46 kVA assuming all 8 drives operate simultaneously.
If 4 drives operate at a time, the power dissipation would be 11.5 kVA]