System information
Manual:System/UPS
60
serial="QS0030311640" manufacture-date="07/18/00"
nominal-battery-voltage=24V
[admin@MikroTik] system ups>
Runtime Calibration
Command: /system ups rtc <id>
The rtc command causes the UPS to start a run time calibration until less than 25% of full battery capacity is
reached. This command calibrates the returned run time value.
Note: The test begins only if the battery capacity is 100%.
Monitoring
Command: /system ups monitor <id>
Property Description
battery-charge () the UPS's remaining battery capacity as a percent of the fully charged condition
battery-voltage () the UPS's present battery voltage. The typical accuracy of this measurement is ±5% of the maximum
value (depending on the UPS's nominal battery voltage)
frequency () when operating on-line, the UPS's internal operating frequency is synchronized to the line within
variations within 3 Hz of the nominal 50 or 60 Hz. The typical accuracy of this measurement is ±1%
of the full scale value of 63 Hz
line-voltage () the in-line utility power voltage
load () the UPS's output load as a percentage of full rated load in Watts. The typical accuracy of this
measurement is ±3% of the maximum of 105%
low-battery (yes | no) only shown when the UPS reports this status
on-battery (yes | no) Whether UPS battery is supplying power
on-line (yes | no) whether power is being provided by the external utility (power company)
output-voltage () the UPS's output voltage
overloaded-output (yes | no) only shown when the UPS reports this status
replace-battery (yes | no) only shown when the UPS reports this status
runtime-calibration-running
(yes | no)
only shown when the UPS reports this status
runtime-left (time) the UPS's estimated remaining run time in minutes. You can query the UPS when it is operating in the
on-line, bypass, or on-battery modes of operation. The UPS's remaining run time reply is based on
available battery capacity and output load
smart-boost-mode (yes | no) only shown when the UPS reports this status
smart-ssdd-mode () only shown when the UPS reports this status
transfer-cause (string) the reason for the most recent transfer to on-battery operation (only shown when the unit is
on-battery)