User Guide
SF100 Installation Instructions for the RIA10-1-SAA Control Panel
1. Mount the RIA10-1-SAA control panel on a wall next to the SF100 Glycol Feed System.
2. Cut the plug-in end of the tank float cord
3. Push the float cable through strain relief fitting in control panel and connect float wires to
terminals 1 and 2 on terminal strip. Connect ground wire to ground connection. Tighten strain
relief nut to secure cable into panel.
4. Connect DCS wiring to remote alarm dry contacts as requested to provide alarm signal.
5. To disable the audible alarm, remove the jumper on the control board.
6. Plug pump cord into RIA10-1-SAA panel.
1
2
3
4
5
NC
NO
COM
FLOAT
SWITCH
TO DISABLE AUDIBLE ALARM REMOVE JUMPER
NOTE: LOW VOLTAGE WIRE INSULATION MUST BE
APPROVED FOR 300V
FLOAT SELECT IS FACTORY SET TO N/O. N/C CAN BE
SELECTED BY MOVING THE FLOAT SELECT JUMPER
TO POSITION 1-2