NT25 CONDENSATE NEUTRALIZATION TANK
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
Installation Instructions
NOTE - Check with your local water authority for regulations regarding discharge of treated
condensate to the drain or sewer system.
WARNING
- “Risk of damage to appliance”. The neutralization tank inlet and discharge must be at a
lower elevation than the condensate drain from appliance.
- Do not allow exhaust flue gases to vent through the neutralization kit. All condensate drains
must have a trap to prevent flue gas leakage. Flue gas leakage can cause injury or death
from carbon monoxide.
- Connection to the appliance and neutralization kit must be installed to ensure that no
condensate backflow into the appliance can occur.
Set the neutralization tank on a secure and level base. Connect appliance condensate drain to the inlet
using corrosion resistant piping. Do not route the condensate line through any area that is exposed
to freezing temperatures. If traffic poses a risk, install some protection to prevent movement
and/or damage. Ensure that no air pockets will remain or form in the piping and that the condensate
will flow freely from the appliance condensate drain into the tank and then to the drain.
Operation
The appliance condensate will flow through the neutralizing media, raising the pH of the
condensate to a level that will help prevent corrosion of the domestic drain and the public
sewer system.
Maintenance
Monitor the level of the neutralization media in the tank periodically. The pH can be checked after
the condensate has exited the tank or by removing the lid and taking a sample from the last
chamber before the outlet. Use a suitable pH test strip paper or an electronic pH meter for precise
measurement. The neutralizing media should be replaced when the pH level drops below the
minimum level of the local water authority. For replacement LipHter media contact your local
Axiom distributor or visit www.AxiomInd.com for more information.