Product Overview

DIRECTIONS:
Add 1 bottle (500 mL or 16.9 oz.) of AXI-THERM CLEAN 5 for every 100 litres (25 gallons) of
water (Dosage: 0.5 %). Use an AXI-THERM INJET to add the product to the system. It must
circulate for at least 2 days when using the existing system circulator. The product may remain in
the system for up to 30 days and the boiler may be on or off during the cleaning period.
Flushing the system with the AXI-THERM TOPFLUSH (flush cart) can reduce the cleaning
operation to 2 to 4 hours. Once the cleaning operation is completed, the system should be well
drained and rinsed. Rinsing should continue until the water runs clear.
If the water does not run clean, repeat the cleaning session. Refill the system with demineralized
water provided by an Axiom PUROPAL demineralizer. Add AXI-THERM PROTECT 1 for
complete system protection.
ENVIRONMENTAL AND SAFETY INFORMATION:
For professional use only.
Before adding to the system, ensure that the system water does not contain other chemicals.
Lower concentrations do not yield satisfactory results. Higher concentrations have no adverse
effects.
Do not use in potable water systems. Do not ingest. Do not dispose of waste through the
environment. Keep out of reach of children. The product is not classified according to the
Globally Harmonized System (GHS).
ACCESSORIES
INJET – Reusable chemical injection bottle 2 litre (0.5 U.S. gallon) capacity
BIO-TEST – Detects the presence of bacterial colonies in low temperature hydronic systems