Product Overview
DIRECTIONS: 
Add 1 bottle (500 mL or 16.9 oz.) of AXI-THERM CLEAN 3 for every 100 litres (25 gallons) of 
water (Dosage: 0.5 %).  Use  an  AXI-THERM  INJET  to  add  the product to  the  system. It must 
circulate for at least 2 days when using the existing system circulator. The product may remain in 
the system for up to 30 days and the boiler may be on or off during the cleaning period. Flushing 
the system with the AXI-THERM TOPFLUSH (flush cart) can reduce the cleaning operation to 
2 to 4 hours. Once the cleaning operation is completed, the system should be well drained and 
rinsed. Rinsing should continue until the water runs clear. If the water does not run clean, repeat 
the  cleaning  session.  Refill  the  system  with  demineralized  water  provided  by  an  Axiom 
PUROPAL demineralizer. Add AXI-THERM PROTECT 1 for complete system protection. 
ENVIRONMENTAL AND SAFETY INFORMATION: 
For professional use only. 
Before  adding  to  the  system,  ensure  that  the  system  water  does  not  contain  other  chemicals. 
Lower  concentrations  do  not  yield  satisfactory  results.  Higher  concentrations  have  no  adverse 
effects. 
Do  not  use  in  potable  water  systems.  Do  not  ingest.  Do  not  dispose  of  waste  through  the 
environment.  Keep  out  of  reach  of  children.  The  product  is  not  classified  according  to  the 
Globally Harmonized System (GHS). 
ACCESSORIES: 
 INJET – Reusable chemical injection bottle 2 litre (0.5 U.S. gallon) capacity 
 BIO-TEST – Detects the presence of bacterial colonies in low temperature hydronic systems 