Product Overview

DIRECTIONS:
Add 1 to 2 bottles (5 to 10 Litres or 1.3 to 2.6 gallons) of AXI-THERM CLEAN 10 for every
100 Litres (25 gallons) of water (Dosage: 5 – 10 %). Use an AXI-THERM “INJET” to add the
product to the system. It must circulate for 3 to 30 days when using the existing system
circulator. The boiler may be on or off. Once the cleaning operation is finished, the system
should be well drained and rinsed. Rinsing should continue until the water runs clear. Refill the
system with demineralized water provided by an Axiom PUROPAL demineralizer. Add AXI-
THERM PROTECT 1 for complete system protection against corrosion, limescale and sludge
formation.
ENVIRONMENTAL AND SAFETY INFORMATION:
For professional use only.
Before adding to the system, ensure that the system water does not contain other chemicals.
Lower concentrations do not yield satisfactory results. Higher concentrations have no adverse
effects.
Do not use in potable water systems. Do not ingest. Do not dispose of waste through the
environment. Keep out of reach of children. The product is not classified according to the
Globally Harmonized System (GHS).
ACCESSORIES:
INJET – Reusable chemical injection bottle 2 litre (0.5 U.S. gallon) capacity
BIO-TEST – Detects the presence of bacterial colonies in low temperature hydronic systems