Datasheet
108-98014 Rev. C
All specications subject to change. Consult Tyco Electronics for latest specications. 6 of 18
Telecom-, Signal and RF Relays
Cradle Relay S V23054/V23062
AXICOM
Coil Data and operating range
Nominal voltage from 6 Vdc to 220 Vdc
Typical nominal power consumption, at 20 °C 1 W
Class of the operative range
acc to EN 61810-1 / IEC 61810-1 and VDE 0435 Part 201
2
Operating voltage (according to the coil type) max. 92% of the nominal voltage
Terminals:
Coil with 1 winding
Start 4 End 1
Coil with 2 windings (upon request)
Start 3 End 2 for winding I
Start 4 End 1 for winding II
The minimum voltage U
I
depends on the contact set and the ambient temperature, the maximum voltage U
II
only depends on the ambient temperature.
Between minimum voltage U
I
tamb
and operating voltage U a safety margin of approx. 20% is recommended.
U
I tamb
(1.2) < U
I
≤
U
II tamb
U
I tamb
= U
I
· U
20 °C
· k
I tamb
U
II tamb
= U
Il 20 °C
· k
II tamb
t
amb
= Ambient temperature
U = Operating voltage
U
I tamb
= Minimum voltage at ambient temperature, t
amb
U
II tamb
= Maximum voltage at ambient temperature, t
amb
k
I and
k
II
= Factors
Note: Instructions for impulse operation
see data sheet cradle relay N
Ambient temperature t
amb
[°C]