User's Manual
Table Of Contents
- 1 SYSTEM DESCRIPTION
- 2 REPEATER INSTALLATION
- 2.1 Requirements
- 2.1.1 Service Antenna Requirements (English)
- 2.1.2 Service Antenna Requirements (French)
- 2.1.3 RF Cable Installation Guidelines
- 2.1.4 Grounding Wires Requirements
- 2.1.5 Power Requirements
- 2.1.6 Optic Cables Guidelines
- 2.1.7 EMV Protection
- 2.1.8 External Alarm and Relay Considerations
- 2.1.9 Location Criteria
- 2.2 Standard Repeater Installation
- 2.2.1 Overview
- 2.2.2 Unpacking and Accessories
- 2.2.3 Rack Mount Installation
- 2.2.4 Wall Mount Installation
- 2.2.5 Grounding
- 2.2.6 Optic Fibre Connection
- 2.2.7 Service Antenna Connections
- 2.2.8 Power Connections and Power On
- 2.2.9 Optional - External Alarm and Relay Connections
- 2.2.10 Closing and Securing the Repeater
- 2.3 Repeater with Fan Hood Installation
- 2.4 Five-Band System Installation
- 2.1 Requirements
- 3 OPENING A SESSION AND NAVIGATING GUI
- 4 MBF-40 COMMISSIONING
- 5 MBF-40 FULL GUI DESCRIPTION
- 6 MONITORING AND FAULT SOURCING
MBF-40 AMERICAS REPEATERS
PRODUCT DESCRIPTION AND USER’S MANUAL
www.cobham.com/wireless
Page | 2-14
Date: 14-Feb-16
Rev. 4.3
Cobham Wireless – Coverage
Document number: 00071UM
2.2.4.2 Wall Marking and Drilling
WARNINGS!!
• Due to the weight of the Repeater, it is NOT recommended to fix to a hollow
wall).
• The Repeater wall mount brackets assembly should be fixed to a solid wall
(these include brickwork, block work, and concrete).
• Always check that there are no pipes or cables hidden in the wall beneath the
area to be drilled. Various pipe and cable detectors are available for this type of
inspection.
• To provide secure fixing to a solid wall, the most common method is drilling and plugging. The
size of fixing is dependent on the item to be fixed and the nature of the wall, The Repeater
should be fixed with mild steel, M6 (50mm to 75mm) rawlbolts or similar.
• Care must be taken to ensure the alignment of the four fixings. A spirit level or plumb line should
be used to ensure horizontal/vertical alignment.
Figure 2-8: M6 Rawlbolt – recommended for wall mount.