User's Manual

Table Of Contents
SMR 700 800 HIGH POWER PS NFPA CLASS B SIGNAL BOOSTER
PRODUCT DESCRIPTION AND USER’S MANUAL
Cobham Wireless Coverage
Date: 23-Nov-16
www.cobham.com/wireless
Doc. No.00060CDUM Rev. 3.4 Page | 25
3.4.4 Connecting Power and Power-Up
CAUTION!!
DO NOT POWER-ON the Signal Booster without either the antennas being connected or the antenna
connections terminated with dummy loads.
This equipment can either be installed indoors or outdoors. When installing OUTDOORS, wet conditions
increase the potential for electric shock when installing or using electrically powered equipment. To
prevent electrical shock when installing or modifying the system power wiring, disconnect the power
source before working with uninsulated wires or terminals.
The Signal Booster operates from a 48VDC power source either UPS or Cobham Wireless Battery Charger
(ordered separately). The power connection differs according to the power source:
3.4.5 Power Connection to UPS
To connect the power to UPS
Use supplied DC cable (P/N 40WVC70900)
Verify the UPS is set up.
Connect 48VDC from the UPS or AC to DC converter (depending on the installation) to the Booster
Power Connector
Figure 3-18 Booster to UPS Power Connections
The cable pinout is as follows:
Pinout Color Label
1 N.C.
2 RED -48V RTN
3 N.C.
4 BLACK -48V
UPS
Booster to UPS
(P/N 40WVC70900)