User's Manual

Table Of Contents
D-MBR 3707-3708 PS NFPA CLASS B SIGNAL BOOSTER
PRODUCT DESCRIPTION AND USER’S MANUAL
Cobham Wireless Coverage
Date: 6-Set-15
www.cobham.com/wireless
Doc. No. 00060CDUM Rev. 1.0 Page | 25
3.8 Booster Dry-Contact Alarm Connections
This section describes the dry-contact alarm connections for the
booster
.
The D-MBR and its power source (UPS or Battery Charger), each provide dry-contact alarms towards
the Fire Department Control Box. (In installations with UPS, refer to your UPS manual for instructions
on dry-contact alarm connections to the Fire Department Control box).
Note the following:
The alarms can be connected any time, before or after the system is powered-on.
The Charger alarm connections are described in section
4.4.7.
Optionally, the Battery Charger Fail and AC Input Fail from the UPS or Charger can be connected
to the Booster alarms (requires GUI configuration as well.
Figure 3-16. D-MBR PS NFPA with Charger Architecture
3.8.1 Load Restrictions
3.8.1.1 Alarm Dry Contact Output Restrictions
Maximum switching voltage: 220 VDC, 125 VAC
Maximum switching current: 2A
3.8.1.2 External Alarm Input Restrictions
Maximum repetitive reverse voltage: 28 V
Impedance load: 470 Ohm
“0” - 0V
“1” - 3.8V - 28V