Axell BSR 3308-PS NFPA
Product Description and User’s Manual
© Axell Wireless Ltd Doc PN 4000004131 Rev. 2.7 23
3.10.4 Summary Alarms Trigger Criteria
The Summary alarm (pins 4 and 7) is triggered under one (or more) of the following:
• PA Current from FF OR
• Channeler Current OR
• Temperature High OR
• PLL Lock
• Repeater power OFF
The summary alarm pins respond as follows:
STATUS
External Alarm on USER connector
RESULT
Power OFF Contacts 4,7 OPEN ALARM
Power ON Contacts 4,7 CLOSE NO ALARM
Summary
ALARM Active
Contacts 4,7 OPEN ALARM
3.10.5 BSR 3308-PS NFPA Installation Alarm Connections
The Repeater Alarm connector contains two sets of dry contact alarms that are
connected to the Fire Department Control Box (see sections
3.10.1 and 3.10.2 above).
• Antenna Malfunction (VSWR) (Pins 3,6)
• Summary (Pins 4,7)
Figure 3-10. BSR 3308 PS NFPA Architecture