© Axell Wireless Ltd Doc PN 4000004131 Rev. 2.7 21
3.9.2.2 For DC repeater models:
• Make sure to fully charge the ±48VDC trickle charge battery.
• Connect the cable from a ±48VDC battery to the repeater DC Power port.
NOTE: System power-up may take up to a few minutes.
Figure 3-8. NFPA Battery Power Connections
3.10 Dry Contact Alarm Connections
Notes: The alarms can be connected any time, before or after the system is powered-on.
For an illustration of NFPA connections, see section 3.10.5.
3.10.1 General
The Repeaters’ front panel Alarm connector provides two types of alarm connections:
• External (Input) Alarms - connected to external sources such as Repeater Door.
To activate the External alarms:
• Connect – Pin-1 (Ext Alarm-1) Pin-5 (GND) to the desired alarm source
(i.e. Repeater Door). For another External Alarm, repeat for Pin-2 and Pin-
5.
• Any generated alarms can be viewed in the Alarms tab.
• Dry Contact – two dry-contact Normally Closed output alarms that are dedicated to
the following:
• VSWR alarm – pins 3 and 6
• Booster Summary alarm – pins 4 and 7