3.7.2.5 -48V Power Source Connection
Note: The -48VDC version of the power supply is designed to turn off if the supply voltage falls below
-36V (
±
1V), not to drain the feeding battery. It will turn on again as the supply voltage reaches -43V
(
±
1V).
-48V power supply requirements
The 48VDC power supply must comply with SELV requirements, as defined in EN60950, which
implies double isolation. The output power needs to be 48VDC +25%/-15%. The maximum input
current is 8A.
Connect the power cable to the plinth as show below:
• Phase linked to the Brown cable
• Neutral linked to the Blue
• Ground to the Green and Yellow. See illustration below.
Figure 3-19: -48VDC Power Connections
Recommended cable areas for 48VDC
Distance Cable Area
0 - 10 meters between repeater and
power supply
2,5 mm²
10 – 50 meters between repeater and
power supply
4 mm²
Over 50 meters between repeater
and power supply
Recommendation is to reconfigure the
installation, or to make special
arrangements to increase cable area