Document Name: Common Commands and Attributes v1.3.0 Revision: 1.2
test phase.
Format:
<Off-time>
where <Off-time> is the number of seconds in off state.
Example:
GET RTF
Reply:
3
means that the relay is in off state for 3 seconds.
Example:
SET RTF 2
changes this value to 2 seconds.
7.18 ACT ACK – Acknowledge Alarm
7.18.1 Overview
This action acknowledges alarm log entries, causing them not to be transferred to
the Axell Element Manager.
7.18.2 Usage
Attribute type: Write-Only Action
This action acknowledges entries in the alarm log and requires Read and Write
access when logged in. Via SMS, this can only be performed by the Main Address.
Format:
ACT ACK <SysEvent>
X is alarm log entry having system event numberssage number <SysEvent>, which
might be a number in the interval 0..231.
Example:
ACT ACK 197
acknowledges alarm with system event number 197
Note! No reply is given to this action (unless a illegal command or system failure
occurs). This means that acknowledging non existing alarms or alarms already
being acknowledged is possible.
7.19 ACT CLO – Clear Alarm Log
7.19.1 Overview
Executing this action clears the alarm log.
7.19.2 Usage
Attribute type: Write-Only Action
Common Commands and Attributes 35/123